Appleton/ATX IEC Hazardous Locations Reference Guide

For a printable explanation of the IEC designations, download this Appleton/ATX IEC Hazardous Locations Reference Guide (English or French) in PDF format.

What is I.E.C.?
The International Electrotechnical Commission writes technical standards including the 79 series and is comprised of nations throughout the world including Canada

Class I
Flammable Gases, Vapours or Liquids

Class II
Combustible Dusts
Class III
Ignitable Fibers
and Flyings
Division System Zone System    
  Zone 0
Ignitable concentrations of gases, vapours, or liquids are continuously present under normal operating conditions
   
Division 1
Ignitable concentrations of gases, vapours, or liquids may be present under normal operating conditions
Zone 1
Ignitable concentrations of gases, vapours, or liquids may be present under normal operating conditions
Division 1
Ignitable concentrations of combustible dusts may be present under normal operating conditions
Division 1
Ignitable concentrations of fibers may be present under normal operating conditions
Division 2
Ignitable concentrations of gases, vapours, or liquids are not likely present under normal operating conditions
Zone 2
Ignitable concentrations of gases, vapours, or liquids are not likely present under normal operating conditions
Division 2
Ignitable concentrations of combustible dusts are not likely present under normal operating conditions
Division 2
Ignitable concentrations of fibers are not likely present under normal operating conditions
Class I Groups
Division 1 and 2:
A (acetylene)
B (hydrogen)
C (ethylene)
D (propane)
Class I Groups
Zone 0, 1 and 2
IIC (acetylene and hydrogen)
IIB (ethylene)
IIA (propane)

Class II Groups
Division 1 and 2:
E (metal dusts)
F (coal)
G (grain)

Class III Groups
None

Note: There is no IEC system that covers CEC Class II and Class III.

T-Ratings
Heat producing equipment is marked with a Temperature Code, to indicate the maximum surface temperature.
"T" Code (Division System) T1 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
"T" Code (Zone System) T1 T2         T3       T4   T5 T6
Max. Surface Temp. (°C) 450° 300° 280° 260° 230° 215° 200° 180° 165° 160° 135° 120° 100° 85°
Note: There are no intermediate "T" ratings (e.g. T2A) in the Zone system

Zone System Protection Methods
Area where product can be used Letter Designation Of Protection Type of Protection
Zone 0   ia Intrinsically Safe (Apparatus is incapable of releasing enough energy to cause an explosion)
Zone 1   m Encapsulation (Arcing devices enclosed in Resin)
    d Flameproof (Enclosures can contain an internal explosion)
    e Increased Safety (Enclosures do not allow the ingress of hazardous gases)
    ib Intrinsically Safe (Apparatus is incapable of releasing enough energy to cause an explosion)
    o Oil immersion (Arcing devices enclosed in Oil)
    q Powder Filling (Arcing devices enclosed in finely ground powder)
    p Purged/Pressurized (Pressure higher than surrounding area maintained within enclosure)
Zone 2   nC Nonincendive (Hermetically Sealed)
    nA Non-Sparking Device (Non-arcing device)
    nR Restricted Breathing (Enclosures restrict the ingress of hazardous gases)

Hazardous Location Markings
Class I, II & III, Division 1 and 2
Required: Class(es), Division(s), Gas/Dust Group(s), Temperature Code.
Example: Class I, Division 1, Group C & D, T4A
Optional: Class1, Zone1, Group IIB IIA T4
Class I, Zone 0, 1 and 2
Required: Ex, Protection Method(s), II, Gas Group(s), T Temperature Code.
Example: Ex de IIB T4
Optional: Class1, Zone1, Group IIB T4

IEC Product Markings Clarification
Ex Indicates suitability for use in hazardous locations.
de Indicates type "d" and "e" protection.
II Indicates "Above Ground" usage.
C Indicates group IIC gases.
T6 Indicates T6 temperature rating.
Comparing Zone and Division Systems
(Only typical Methods of Protection Listed)
Zone 0 Division 1
Intrinsically Safe "ia" Class I Division 1 Equipment
Zone 1
Division 1 Approved
Flameproof "d"
Increased Safety "e"
Zone 2 Division 2
Zone 0 and 1 Equipment
Division 2 Approved
Non-Sparking "n"
Division 1 and 2 Equipment
Flameproof "d"
Increased Safety "e"
Non-Sparking "n"
Note: Division/Zone 1 represents about 5% while Division/Zone2 represents about 95% of a typical Canadian hazardous petrochemical area.

IEC Ingress Protection IP Ratings
Typically a two-digit number
Protection Against Solids   Protection Against Liquids

0 - No Protection.

1 - Protected against solid bodies larger than 50mm. e.g. Hand.

2 - Protected against solid bodies larger than 12mm. e.g. Finger.

3 - Protected against solid bodies larger than 2.5mm. e.g. Tool, wires. (Type 1)

4 - Protected against solid bodies larger than 1.0mm. e.g. Small wires.

5 - Protected against dust. No harmful deposits. (Type 5)

6 - Completely protected against dust.

 

0 - No Protection.

1 - Protected against vertically falling drops. e.g. Condensation.

2 - Protected against falling drops of water tilted 15 degrees from vertical. (Type 2)

3 - Protected against falling rain, tilted 60 degrees from vertical. (Type 3)

4 - Protected against splashing water from all directions. (Type 3R)

5 - Protected against jets of water from all directions. (Type 4)

6 - Protected against jets of water of similar force as heavy seas from all directions.

7 - Protected against effects of immersion. (Type 6)

8 - Protected against effects of submersion.
 

Note: Equivalent CSA Type (Nema), indicated in parenthesis. A third digit is occasionally used, and reflects the effects against mechanical forces.

Main Differences Between Zone and Division Systems
Non-metallic enclosures and fluorescent light fixtures (Increased Safety "e") are permitted in a Zone 1 Area. The enclosures are to have special seals (Ingress Protection IP54 see Table above) and use special nonloosening terminal blocks. The fluorescent light fixture has to incorporate an automatic electrical disconnect upon entry into fixture.   Although a significant change, it is important to note that a Zone 1 area represents only 5% of a typical Canadian petro-chemical facility.

Higher "T" ratings achieved for Zone 2 HID light fixtures (Restricted Breathing Ex nR). The "T" rating is based on the highest exterior temperature.

 

This allows for the use of less expensive light fixtures. A strict and possibly costly maintenance program is recommended to ensure the integrity of the seals on the light fixture.


The Cost Factor
Location The Argument
In Europe   In Europe most of a Petro-chemical facility is classified as Zone 1. When comparing the cost of a typical Zone 1 type application to a Division 1 application you will find that there is likely a cost saving for the Zone system.

In Canada and North America   In Canada where 95% of a facility is Zone 2 or Division 2, there have been several studies done, which conclude that the Division system costs less. Since there is very little difference in product used in Zone 2 or Division 2, and that Division equipment is typically less expensive, it can be argued that the Division system will actually cost less.

Conclusion   Many factors (capital, installation, maintenance) including the nature of the facility need to be considered when determining actual cost. The most significant advantage for the user is flexibility in the choice of product that can be used.